MENU
 

Bruno DC System Watchdog Monitor by HindlePower

bruno dc system watchdog monitor by HindlePower

Complete DC system reliability

Bruno DC System Watchdog Monitor is a supervisory system that informs and educates on the health of your entire DC system and provides early warning detection.

Detect battery failures through float current trending, battery continuity and capacity test. Verify charger operation with float voltage trending, ensure system safety with ground fault detection and prevent inefficient system performance with temperature monitoring.

Bruno DC System Watchdog Monitor from HindlePower empowers DC system reliability by detecting the undetected. With built in intelligence, you will have clear insight into your entire DC system and have the peace of mind knowing it is operating properly.

The user-friendly interface paired with the Hindle Health System will allow you to simplify data gathered from your battery, charger, system loads and other DC equipment all while streamlining maintenance procedures to make the job easy. Bruno’s versatile, adaptive technology makes it your true partner in DC system reliability.

What can Bruno do for you?

Float Current Measurement Float current is monitored, recorded and trended over the life of the battery
Temperature Temperature Battery and ambient temperature are monitored, recorded, and trended over the life of the battery
Battery Supply Voltage The float charge voltage, supplied to the battery, is monitored, recorded and trended over the life of the battery
Electrolyte Level The electrolyte level is recorded manually for centralized data collection
Battery Capacity Test Battery Capacity testing per IEEE 450/1106/1188
Active Load Profile Battery current, battery voltage, and charger current is recorded for any event that discharges more than 1A from the battery
Intelligent Ground Fault DC system ground fault detection for all components in circuit
Battery Continuity Verifies continuity of the battery, also known as open battery

Standard Features of Bruno DC System Watchdog

  • Innovative design with a full color, 10.1” LED capacitive touch-screen interface
  • Easy access to reports:
    • Viewable on the LED display
    • Downloaded in standard reports format (PDF)
    • Downloaded for analysis in Excel format (CSV)
  • Fail safe design ensures the battery is always connected to your loads during testing modes or in the event of any component failure
  • 3rd Party equipment alarming for centralized data integration
  • Compliant with NERC PRC-005

System Benefits

  • Meets the requirements for NERC PRC-005 DC system compliance, monitoring and reporting for DC systems
  • Provides detailed outage performance information
  • Early warning for battery failure by monitoring key performance parameters
  • Helps the operator isolate a ground fault within the DC system
  • Simple and easy to use, just like your smart phone
  • Remote communication for alarm indications

Watch Video Overview

Bruno DC System Watchdog by HindlePower

DC System Voltage (Vdc) 24, 48, 130, 260
Continuous Current Rating @ 50 Degrees Celcius (Adc) 50, 100, 150, 200
Charger Size (Adc) 6 - 200A
Battery Disconnect 10kAIC, 20kAIC
Charger Disconnect 10kAIC, 20kAIC
Communications DNP3 Level 2 Ethernet. Modbus Ethernet. Serial
Operating Ambient Temperature 5°F to 122°F (-10°C to 50°C) w/o derating
Operating Altitude 3300 feet (1000 meters) above sea level without derating
Relative Humidity 0% to 95% (without condensation)
Applicable Codes IEEE 946,  NERC PRC-005
Monitoring HindleHealth® System
 

Request Information

Contact us to request Product Information, Place Orders or Ask Questions.

Sales Team

     

Order Support

     

Sales Team

      800.931.4919

Order Support

      800.428.7697

Purchase Order Fax

      800.931.4817

Search All Products