| Input |
| Voltage |
115 or 230 VAC, 50/60 Hz,
single phase |
| Output |
| Voltage |
120 VDC (Nominal) |
| Current |
10 or 20 Amps |
| Regulation
|
±1%
load and line |
| Current limit
|
Rectangular current limit,
adjustable from 5% to 100% |
| Modes |
Float, equalize and auto-equalize
(with built-in timer), and boost mode when used as a charger.
|
| Efficiency |
>85% typical |
| Protection |
| AC Line Filtering |
Common mode and differential filtering |
| AC Circuit Breaker
|
2-pole |
| DC Circuit Breaker |
2-pole |
| Brownout & Transient |
Yes |
| Overload & Short Circuit |
Yes |
| Reverse Battery Polarity |
Yes |
| Isolation |
>1500V rms per IEC 255-5
(1977) |
| Surge Withstanding |
ANSI/IEC C37.90
(1989) |
| Ripple/Noise
|
100mV maximum |
| Status Alarms
|
Composite AC fail / low
voltage alarm with Form-C contacts, and visual indication. |
| Controls
and Indicators |
- Digital voltmeter / ammeter for output monitoring
- Input / output circuit breaker
- Power and status indicators
- Float, equalize and boost adjustable controls; all with LED
indicators
- Heavy duty compression type input / output terminals
- Separate load and battery terminals
|
| Environmental |
| Operating Temp Range
|
-10°C to +50°C |
| Storage Temp Range |
-40°C to +85°C |
| Non-condensing Humidity |
0 to 95% RH |
| Enclosures |
| Mounting
|
19-inch rack mount with carrying handles |
| Dimensions |
3RU high for 10 Amp output units; 5RU high for 20 Amp output
units; 18-inches deep |
| Colour |
Black epoxy paint, light textured |