| Input |
MajorTHS30/48-RECT |
MajorTHS50/24-RECT |
| Input Voltage |
176 VAC - 275 VAC, single phase
150 VAC - 176 VAC: Derated to 80% Load
90 VAC - 150 VAC: Derated to 50% Load |
| Input Current |
<12 Amps (Low Line Input. Full-Load) |
| Line Frequency |
45 - 65 Hz |
| Power Factor |
>0.99, 220 VAC (Full-Load) |
| THD |
<5%, 220 VAC (Full-Load) |
| Efficiency |
>90% @ Full Load, 220 VAC |
>88% @ Full Load, 220 VAC |
| Inrush Current |
<12 Amps (peak), Nominal Input, Full-Load, Cold Start |
| Start Time Delay (Walk-in) |
3 - 10 Seconds |
| Protection |
Fuse |
| Output |
| DC Output Voltage |
40 - 60 VDC |
20 - 29 VDC |
| Output Power |
1800 Watts: (0°C to +50°C)
1500 Watts: (0°C to +65°C)
|
1500 Watts: (0°C to +50°C)
1200 Watts: (0°C to +65°C)
|
| Regulation |
Load: <±0.5% (Load 0 - 100%); Line: <±0.1% (Load 0 - 100%) |
| Current Limit |
<110% of rated Output Current |
| Noise |
Audio Band: <2mV CCITT
Wide Band: <20mVrms (10 Khz - 100 MHz)
Acoustic: <55dBA @ 1M |
| Temperature Coefficient |
<200ppm / °C |
| Current Sharing |
<5% of Rated Output Current |
| Protection |
Fuse |
| Protection |
| AC Input Voltage High |
Automatic Shutdown and Recovery |
| AC Input Voltage Low |
Automatic Shutdown and Recovery |
| Brown-Out |
No Damage During Brown Out Conditions |
| Output Short |
Automatic Shutdown and Recovery |
| Output Current |
Automatic Shutdown and Recovery |
| High Voltage Shutdown |
If rectifier module voltage exceeds preset value, module will shut down and latch |
| Over Temperature |
Automatic Shutdown and Recovery |
| Environmental |
| Current Harmonic |
EN 61000-3-2/A12, EN 60555-2, IEC 1000-3-2 Class A |
| Voltage Fluctuation |
EN 61000-3-3, EN 60555-3 |
| Electrostatic Discharge |
EN 61000-4-2, IEC 1000-4-2,
IEC 801-2 Level 4, 15KV Air Discharge, 8KV Constant Discharge |
| Radiated Susceptibility |
IEC 1000-4-3, IEC 801-3 Level 3, 10V/m |
| Electrical Fast Transients |
EN 61000-4-4, IEC 1000-4-4, IEC 801-4 Level 4, 4KV |
| Conducted Susceptibility |
IEC 1000-4-6 Level 3, 10V/m |
| Lightning/Surge |
ANSI/IEEE C62.41-1991 B3, IEC 1000-4-5 Level Special (6KV) |
| Status/Alarm Indicators |
| AC ON |
Green LED |
| Rectifier Failure Alarm (RFA) |
Red LED |
| Current Limit (CL) |
YellowLED |
| Adjustments |
| Current Limit (CL) |
Setting from System Controller (SMR or CSU) |
| Float Voltage (FLO) |
Setting from System Controller (SMR or CSU) |
| Test Points (I+,I-) |
Output Current Test |
| Remote Control |
Emergency Shut Down, Float / Equalize Mode, Current Limit |
| Physical |
| Dimensions |
3.3"W x 5.2"H x 10.35"D (84 x 132 x 263mm) |
| Weight |
7.26 lbs / 3.3 kg |
| Cooling |
Fan Cooling |
| Heat Dissipation |
682 BTU / Hour Max. Per Module |
698 BTU / Hour Max. Per Module |
| Approvals |
| Safety |
UL / cUL (Meets IEC 950), TUV / CE (Meets EN 60950) Approvals |
| MTBF |
>150K Hours |