| Maximum Continuous Operating Voltage |
25% above nominal |
| Remote Indication Contacts |
NO/NC, rate 125 VAC, 2A |
| Module Diagnostics |
Green LED mechanical (fuse link operated) flag red LED |
| Standard Fuse Disconnect |
600 VAC; 200,000A RMS Symmetrical rating; 200,000 AIC fusing |
| Redundant Protection Stages In All Modes |
Each molde contains dual independant redundant protection circuits |
| Enclosure |
NEMA 1, 2, 3, 3S, 4, 4X, 12, and 13. Transparent cover for maximum visibility and safety. |
| Operating Environment |
-40°C to 85°C, relative humidity (non-condensing) |
| Construction |
Ultra low impedance assembly. Modules are bolted to a corrosion resistant, tin plated coper bus bar. Non plug-on modules in the surge path. |
| Terminal Lugs |
#2 AWG max wire size |
| Mounting |
0.31" diameter holes (16.75" x 12.00")
(enclosure can be easily drilled for cable access) |
| Module Replacement |
Remove two bolts, unplug remote indication connector and remove module. Estimated replacement time: 2 minutes. |
| Module Dimensions |
1.25" x 5.3" x 2.5" (3.2cm x 13.5cm x 6.4cm) |
| Dimensions |
16" x 14" x 7" (42cm x 37cm x 18cm) |
| Weight |
Approximately 20 lbs |