| Operation |
| Nominal Input Voltage |
120/208/240, 60Hz (220/230, 50Hz Available) |
| Input Voltage Range |
+15%, -20% |
| Nominal Output Voltage |
120/208/240, 60Hz (220/230, 50Hz Available) |
| Output Voltage Regulation |
±3% for input voltages + 15%
to =20% |
| Output Voltage Waveform |
Sine Wave |
| Output Voltage THD |
5% or less at rated kW load |
| Overload Capacity |
150% surge & 125% for 10 minutes
online; 150% & 110% for 10 minutes on inverter |
| Transfer Time |
0 ms |
| Lightning, Surge and Noise Protection |
2000: 1 spike attenuation using ANSI/IEEE
C62.41 and C62.45 Category A and Category B tests. Common Mode ->120
dB.Normal Mode ->60dB |
| Safety Certification |
UL, CSA, cUL, CE |
| EMI Compliance |
Hot-swappableFCC Class A |
| Testing Standards |
ANSI/EEE C62.41 (1980); ANSI/EEE C62.45
(1987); IEC 801-2, 801-4, 801-5 |
| Communication |
RS-232 serial port (DB-25), plus contact
closures |
| Environmental |
| Operating Temperature |
0 to 40°C |
| Storage Temperature |
-20° to + 60°C |
| Relative Humidity |
5 to 95% without condensation |
| Altitude |
3050 m (10,000 ft) Maximum |