| Input Voltage:
|
115 or 230 VAC, ±20%, 48-410 Hz
Standard. Other inputs available. |
| Input Protection
|
Thermal fuse and Inrush current
limiting. |
| Input Isolation |
Input-chassis / Input-output / Output-chassis:
2250VDC |
| Output Voltage
|
120/208 VAC/60 Hz; (230/400 VAC/ 50 Hz and 115/200 VAC/400 Hz Available.)
Continuous output with grounded neutral. Isolated floating output available. |
| Efficiency
|
Min 78% at full load |
| Line Regulation |
Maximum 0.5% |
| Load Regulation |
Maximum ±6% from 10% load to full
laod |
| Output Protection
|
Current limiting with short circuit
protection.
Thermal shutdown with automatic reset in case of
insufficient airflow |
| RFI Suppression
|
Meets requirements of EN 55022:
1987 Class B conducted emissions |
| Crest Factor
|
Maximum 3.0 at 90% load |
| Harmonics (THD)
|
Less than 5% |
| Operating Temp.
|
0°C to +50°C (internal fan)
|
| Temp. Drift
|
0.05% per°C over operating temperature
range |
| Dimensions
|
5.3"H x 16.75"W x 13.8"L (Enclosed
Case) |
| Connections
|
Input: Compression-type terminal.
Output: Standard AC Receptical |
| Weight
|
25 pounds (11.35Kg) |
| Warranty |
Twelve months subject
to client application within accepted engineering
practice.
Designed to meet common approval requirements. |